Utilize "Free Cooling" to reduce carbon emissions while
lowering operational cost with Water-Side Economizers
Limiting chiller operation-a practice dubbed "free cooling"-is
intriguing, for "reducing the number of hours of chiller operation
has a larger impact on lowering energy use in a facility than
by selecting a more energy-efficient chiller" (Sorell, 2007).
Users with an existing chilled water infrastructure can accomplish
"free-cooling" via a supplemental heat exchanger called a Water-Side
Economizer.
What is a Water Side Economizer?
Using this economizer, there are no noticeable changes on
the data center floor. The same collection of air handlers,
raised floors, and fans move air as they normally would. The
change occurs behind the scenes in the production of the chilled
air and the removal of waste heat.
A water-side economizer eliminates the need for cooling via
compressors. When environmental conditions are optimal, the
warm return water from the data center is routed to the economizer.
There, condenser water accepts this heat and ultimately rejects
it to the atmosphere via a dry cooler or evaporative tower.
Returned to its desired temperature, the chilled water supply
then returns to the data center air handlers.
Water-side economizer operation depends on ambient conditions.
The outside air must sufficiently cool the condenser water to
allow for proper heat exchange between the two loops.
Water-Side Economizer: Configuration
During the EPA's 2006 Conference on Enterprise Servers and
Data Centers, Oracle addressed an economizer retrofit, where
space was a particular concern. The economizer is installed
between the chiller and the data center. The additional parts-
new "pipes, valves, and controls,"- require physical space which
existing facilities may not have (Oracle, 2006). In addition,
the controls- switching between economizer and mechanical cooling,
were not well defined. Any irregularities could comprise cooling
on the data center floor.
Their experience stresses the importance of design. A data
center at the design stage can allocate the space and engineer
the controls in advance. This initial investment positions a
data center to take advantage of a favorable climate for years
to come. Wells Fargo, for instance, built an economizer into
its new Minneapolis facility at a cost of ~$1 million and saved
$150,000 during its first year of operation. The bank envisions
saving up to $450,000 annually on its energy costs, taking advantage
of the cold seasonal temperatures in Minnesota (Mitchell, 2007).
These advantages are not exclusive to northern geographies.
Despite a milder, more humid climate, UPS achieves some measure
of free-cooling from November through April. A robust building
management system eliminates the complexity of switching between
chiller and economizer operation. This facility is also an example
of a successful retrofit. UPS built the data center in 1995
and brought the economizer online in 2000 (Stansberry, 2008).
Water Side Economizer: Environmental Considerations
Below you will find ASHRAE's recommended envelope for temperature
and humidity on the data center floor:
| ASHRAE TC 9.9 |
Recommended |
Allowable |
| Temperature |
18-27 deg C (64.4- 80.6 Degrees
F) |
15-32 deg C (59-90 Degrees F) |
| Humidity |
5.5-15 deg C Dew Point (41.9-59
Degrees F ) |
20%-80% RH |
** Conditions reflect air ENTERING the
IT equipment**The objective is to use the economizer and comply with ASHRAE's
envelope. To demonstrate an ROI, users must approximate the
economizer's availability, a calculation that involves climate,
chilled water supply temperature, and the ultimate method of
heat rejection.
Dry coolers depend on dry bulb temperatures, making lower
fluid temperatures harder to achieve. Evaporative coolers use
wet bulb temperatures and can attain greater availability as
"cooling towers evaporate water to lower temperatures (Equinix,
2008). With each method, users must consider an approach temperature.
With a 60 degree chilled water supply and a seven degree approach
temperature, the economizer can kick in when ambient conditions
are 53F. The type of technology (dry coolers vs. evaporative
coolers) will impact the approach temperature. With this
data, users can approximate their operating hours.
Maximizing Economizer Efficiency
Water-side economizers allow users to flick the switch on
the compressors for a finite period of time. To demonstrate
a quick ROI, however, they must take additional steps to maximize
the technology.
Containment Strategy
Data centers usually supply very cold water to air handlers
on the data center floor. To consistently produce 42 degree
water, for example, the economizer would require ambient conditions
in the 30s. For most data centers, that's "possible only during
relatively brief periods of extremely cold weather, making it
hard to justify the expense of investing in an economizer" (Intel,
2007). The cold water creates cold air, which counteracts recurrent
mixing of the supply and return airstreams.
If data centers use containment (either cold aisle or hot
aisle), they can potentially raise their chilled water set point.
With intermixing eliminated, perhaps users can now achieve their
desired server inlet temperature with a 55 degree or warmer
chilled water supply. Thus, containment can afford the economizer
additional operating hours.
Elevated Chilled Water Temperatures
The chilled water discussion isn't as simple as raising
the supply temperature. A cooling coil within any data center
air handler is designed with a certain refrigerant supply temperature.
Raising this temperature may be impractical if it affects the
overall capacity of that air handler and the room cooling design.
In addition, the chilled water plant may serve areas other than
the data center; those areas may be adversely impacted with
an increased chilled water temperature.
Yet, there are certain close-coupled products that address
high densities with elevated water temperatures. A higher water
temperature means more hours off the chiller and more hours
on the economizer. A psychrometric chart of San Jose, California,
for instance, shows 5180 hours per year the wet-bulb temperature
falls below 55 degrees F. This temperature can result in 62
degrees F supply chilled water and 70 degrees F inlet air to
the servers, well within ASHRAE's recommended envelope.
Data center provider Equinix, during a 2008 presentation,
uses Baltimore as another example. A 43 degree F water setting
can be achieved approximately 1,900 hours of the year. If the
chilled water temperature can increase to 50 degrees, the operating
window improves to 2,900 hours per year. This availability would
only increase if used with a close-coupled design and an even
higher inlet temperature.
Understanding the Controls
Like its counterpart (air-side economizers), this technology
depends on design and controls to work optimally. Water side
economizers add another level to the cooling scheme, "components
that must be operated and maintained properly-if not savings
will not be realized" (Equinix, 2008). For this reason, the
interactions between the economizer and mechanical cooling must
be seamless and well-defined to ensure on the data center floor
it's business-as-usual.
Conclusion
Facilities with water-side economizers have seen considerable
returns. The aforementioned Equinix study envisions a 5 megawatt
data center in the Northeastern US will save $225,000 a year
through the technology. Their final slide also provides an important
talking point: "The computer room is a critical environment--
(we) can't allow energy efficiency goals to compromise uptime
or the room environmental operating parameters."
This statement highlights concerns about the marriage of
efficiency and availability. Yet the answer is always in the
engineering. A user who spends a little more on initial design
is poised to save even more over the lifetime of his data center.
As they are accustomed, data center professionals must look
beyond the short term-"the perception that designing for efficiency
equates to a larger up-front investment"-and realize the big
efficiency and cost picture: "the lower the PUE, the shorter
the ROI on your investment" (Sun Microsystems, 2008). Circumventing
the chiller, the water side economizer is an asset in designing
to a low PUE, achieving availability/reliability goals, and
conserving considerable energy in this process.

Contact us to find the best Economizer solution
for your cooling needs.

Our engineers can help you select the best
Economizer solution for your cooling needs.
Click here
or Call 1-800-638-2638 for a free Economizer project
consultation.
Bibliography
Bowman, C. (2009, February 3). 'Free cooling'with fresh
air makes McClellan Park data center greener. Retrieved
February 3, 2009, from The Sacramento Bee:
http://www.sacbee.com/business/story/1593883.html?pageNum=1&&mi_pluck_action=page_nav#Comments_Container
Equinix. (2008, March 15). Free Cooling: Economizers in
Data Centers. Retrieved January 28, 2009, from Slideshare:
http://www.slideshare.net/digitallibrary/free-cooling-economizers-in-data-centers
EYP Mission Critical Facilities. (2006, July 26). Energy
Intensive Buildings Trends and Solutions: Data Centers.
Retrieved February 2, 2009, from Critical Facilities Roundtable:
http://www.cfroundtable.org/energy/072106/myatt.pdf
Intel. (2008, August). Reducing Data Center Cost with
an Air Economizer. Retrieved January 28, 2009, from Intel:
http://www.intel.com/it/pdf/Reducing_Data_Center_Cost_with_an_Air_Economizer.pdf
Intel. (2007, May). Reducing Data Center Energy Consumption
with Wet Side Economizers. Retrieved February 10, 2009,
from Computerwoche:
http://www.computerwoche.de/fileserver/idgwpcw/files/1437.pdf
Mitchell, R. L. (2007, November 5). Case Study: Wells
Fargo's Free Data Center Cooling System. Retrieved February
10, 2009, from Computerworld:
http://www.computerworld.com/action/article.do?command=printArticleBasic&taxonomyName=Servers+and+Data+Center&articleId=299301&taxonomyId=154
Oracle. (2006, January 31). Case Study: Expanding an Existing
Data Center. Retrieved January 28, 2009, from Energy Star:
http://www.energystar.gov/ia/products/downloads/MKhattar_Case_Study.pdf
Pacific Gas and Electric. (2006). High Performance Data
Centers: A Design Guideline Sourcebook.
Reuters. (2008, November 17). Red Rocks Data Center Leverages
Mountain Air for a Green Advantage. Retrieved February 3,
2009, from Reuters:
http://www.reuters.com/article/pressRelease/idUS117289+17-Nov-2008+PRN20081117
Rumsey, P. (2007, August 29). Using Airside Economizers
to Chill Data Center Cooling Bills. Retrieved Janaury 28,
2009, from GreenerComputing:
http://www.greenercomputing.com/blog/2007/08/29/using-airside-economizers-chill-data-center-cooling-bills
Sorell, V. (2007, December). OA Economizers for Data Centers.
ASHRAE Journal , pp. 32-37.
Stansberry, M. (2008, January 21). Green UPS Tier IV Data
Center Water-Side Economizers. Retrieved February 10, 2009,
from SearchDataCenter:
http://searchdatacenter.techtarget.com/tip/0,289483,sid80_gci1295380_mem1,00.html
Sun Microsystems. (2008). Energy Efficient Data Centers:
The Role of Modularity in Data Center Design. Sun Microsystems.
Tschudi, W. (2007). Data Center Economizer Contamination
and Humidity Study. Pacific Gas and Electric/Lawrence Berkeley
National Laboratory.
About 42U
Since 1995, 42U has been a leader in providing
data center efficiency
solutions for data center and facilities managers. Our vendor and technology
agnostic approach leverages our best-practice expertise in monitoring, airflow
analysis, power, measurement, cooling, and best-of-breed efficiency technologies
to help data center managers improve energy efficiency, reducing power consumption
and subsequently lowering energy costs.
This work is licensed under a
Creative Commons Attribution-No Derivative Works 3.0
Unported License.
|