Sentry PDU408
For
upgrade options, please call 1-800-NET2NET (638-2638)
The Sentry PDU 408 offers -48 VDC power distribution and
circuit breaker protection per each output connection to support -48 VDC
-powered network equipment units.
The PDU 408 adds versatility to collocate bays that
require additional high-current distribution beyond the main
distribution frame.

Sentry PDU408 Key Features and Benefits:
-
Dual -48 VDC 100-amp Input Power Feed Connections
-
Quantity 8 Output Power Connections
-
Grounding Assembly for earth grounds
-
"Fail Safe" models with steering diodes for
redundant power supply
-
Designed for locally staffed POP sites, NOCs and
equipment rooms
-
25-Amp Circuit breaker protection for each power
output
-
Single-panel access for all wiring and circuit
breakers
-
The Sentry PDU 408 is NEBS compliant
Sentry PDU408 Rack-Mount Enclosure:
1U and 2U "horizontal" rack-mount enclosures are 17" wide and include
standard mounting brackets for 19" cabinet rails. 23" brackets also
available.
Sentry PDU408 NEBS Compliant: Meets NEBS Level
One and Level Three requirements for co-location in a BellCore (Telcordia)
central office.
Sentry PDU408 Fuse-Protected Outlets: Power
Outlet protection provided by fuses.
|
Sentry
PDU 408 Specifications |
|
Item # |
Description |
|
PDU408-0-2 |
PDU 408,
Qty (2) 100-Amp input feeds @ -48 VDC
Qty 8 power outlets with 25-amp circuit
breakers |
|
PDU408-F-2 |
PDU 408,
Qty (2) 100-Amp input feeds @ -48 VDC
with Fail-Safe Steering Diodes for power
redundancy
Qty 8 power outlets with 25-amp circuit
breakers |
|
Operating Voltage |
-12 to
-72 VDC
-48VDC for described amperage values |
|
Mounting
Brackets |
Each PDU
includes two heavy-duty L-shaped
mounting brackets for 19" racks
23" available |
|
Dimensions |
17" (W)
10" (L)
2U |
|
Certifications |
FCC, UL
Standard 1950,
CSA C22-3 #950, TUV EN60905,
NEBS: Level 1 & Level 3,
°°° GR-63-Core, °°° GR-1089-Core |