Sentry Fail Safe Transfer Switch

Sentry Fail Safe Transfer Switch
Sentry Fail Safe Transfer Switch (FSTS)

The Sentry Fail-Safe Transfer Switch (FSTS) features two input power feeds, from separate AC circuits, to supply single-power equipment with dual, redundant power sources. A primary AC circuit provides power to the connected device(s). With this rack automatic transfer switch, if the primary source becomes unavailable for whatever reason, then the Sentry FSTS auto-switches to the secondary power source to support the connected equipment.

The transfer from one power source to the other is seamless to the connected equipment with this rack automatic transfer switch. When the secondary power source is available, an interruption of the primary power source will not affect the equipment's uptime or performance.

Unique to the Sentry FSTS is the ability to designate which power source is primary and which is secondary. With the Primary Select switch, a power engineer simply toggles the switch from primary to secondary, which transfers the load from one power feed to the other. Now, the "secondary" becomes "primary" and the power engineer can safely work on the first power source without dropping power to the connected equipment.

Also exclusive to the FSTS is the ability to select the high voltage (208-230V) or low voltage (110-120V) operating range of the AC power source. Use the Sentry FSTS as a universal power transfer switch for all cabinets and servers, regardless of the voltage. To apply power, just remove a panel and then choose the appropriate voltage range to the Fail-Safe Transfer Switch.

Sentry Fail Safe Transfer Switch Key Features and Benefits:

Sentry Fail Safe Transfer Switch Rack-Mount Enclosure: 1U and 2U "horizontal" rack-mount enclosures are 17" wide and include standard mounting brackets for 19" cabinet rails. 23" brackets also available.

Sentry Fail Safe Transfer Switch 20-amp Power Input Support: 20-amp Power Input Support. IEC320/C20 power inlet receptacles supports any power cord with IEC320/C19 power connector (PTCORD-XX).

Sentry Fail Safe Transfer Switch Voltage Select Feature: User-definable voltage level, select either 110VAC or 208VAC.

ServerTech Sentry FSTS Specifications

Item #Available
Input
Voltages
Rated
Amperage
Available
Input
Cord
OutletsDimensions
 
PTTS-H008-0-02100-120V
or 208-230V
Rated by UL/TUV
at 120V~/20A or 230V~/16A
Input power cables for NEMA 5-20P, L5-20P
or IEC 60320/C19
(8) IEC 60320/C131.75" (L)
8.0" (W)
17.0" (D)

Sentry Fail-Safe Transfer Switch, qty 2 C20 20A power input feeds, qty 8 C13 power outlet receptacles; Fail-safe redundancy between primary and secondary power sources; Primary-Select switch to designate primary power source; Range-Select switch to designate operating range (voltage).
Transfer RangeNominalPull InDrop Out
110-120V90V12V
208-230V173V23V
Branch Circuit ProtectionCompliant to UL CSA 60950-1 1st Edition, April 2005
Indicator LEDs-Confirms power supplied to outlets
-Identifies condition as primary power source or secondary power source supplying power to outlets
Voltage Range Select-Supplies either 100-120V or 208-230V AC voltage ranges
-120V and 230V equipment cannot be intermixed
-All power input feeds must be removed prior to selecting/altering operating range
-Remove Range Select faceplate covering to select appropriate voltage
-Lucite window allows visual confirmation of voltage range
-Switch in "up" position designates 208/230V
-Switch in "down" position indicates 110/120V
Mechanical Integrity-Dual-brace cable retainer brackets on power input feeds
-Clip-style cable-retention retainer brackets at each power outlet receptacle
-Adjustable mounting for front or rear panel, flush or recessed mounting
Standards
> CTUVus - UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUV_GS - EN60950-1:2001
Warranty- One year

ServerTech Sentry FSTS Downloads & Manuals